TECHNICAL NOTE
Input Name Set content
EXECUTE Execution Block enable
REVERSE Direction
selection
The direction of the homing.
0: Seek in forward
1: Seek in reverse
INPUT INPUT input Allocation of INPUT signal
Function block sets to OBxx05B.
AXIS Axis setting Axis number related to the block.
1~16
TYPE Home position
return method
19: “INPUT" is selected.
TIME Timer limit
setting
Maximum time to complete the Homing, if timeout then
Error
TRAVSPD Speed of rapid
feed
Traverse speed in count/second.
0-Max speed (ML3**12)
Moving direction follow the sign of the OFFSET.
APRSPD Approach speed Not used
CRPSPD Creep rate Creep speed in count/second.
0-Max speed (ML3**12)
OFFSET Offset value
Final moving distance. And the position will
be this value. If the value is positive, the
final moving is in the same direction of
homing. If it is negative the final moving will
be in the opposite of homing
File: MP2000_IndividualFunctionDocument_RevC 66/168