TECHNICAL NOTE
ASCII CHARACTER INPUT Function Block
Function block for MP2000 series
<ASCIIIN> Function Block Summary
This function block receives a sequence of 7-bit or 8-bit ASCII characters of a specified size through the
controllers serial port, RS232 or RS422/485 from a transmitter device. This sequence of characters is
then stored in table format at an offset global MW register location.
Function Block Diagram
<ASCIIIN> Function Block Operation Notes
To use the function block, the EXECUTE bit must be held ON.
If the EXECUTE bit goes off during operation, the block will stop receiving data.
On the rising edge of the EXECUTE input, the following two are executed. The
EXECUTE input should be maintained ON while in operation.
o The set value of START and SIZE are read.
o The storage table is initialized by data H2020(Null).
ERROR–ID output has been added to better troubleshoot communication
problems. A zero in the value means no errors or block disabled.
Protocol settings must be configured in controller module setup and transmitter
setup, and must match (baud rate, parity, stop bit, # data bits).
This ASCIIin function block uses a MSG-RCV an embedded function. Since the
transmission protocol is set to none (internal setting =3(no procedure 2)(The data
of each byte is transferred according to a no procedure)), the Master/Slave
setting in module configuration is not necessary.
File: MP2000_IndividualFunctionDocument_RevC 154/168
Doc Number: eng.MCD.05.101 11/17/2005