Main Circuit Terminal Functions
Table 3.1 Main Circuit Terminal Functions
Terminal Description Function Page
R/L1
Main circuit power supply input Connects line power to the bypass 52S/L2
T/L3
U/T1
Drive output Connects to the motor 52V/T2
W/T3
For 208 Vac: 100 Ω or less
For 480 Vac: 10 Ω or less
Grounding terminal 64
u
Wire Gauge and Tightening Torque Specifications
Note: 1. For 0 to 100 A, use a minimum of 60 °C - 75 °C copper wire.
2. For above 100 A, use a minimum of 75 °C copper wire.
3. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient
temperature within 40 °C and wiring distance less than 100 m.
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater
than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to
calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
• Refer to UL Standards Compliance on page 439 for information on UL compliance.
Table 3.2 Main Input Circuit Wiring Tightening Torques and Wire Gauges
Z1000 Bypass
Model Z1B1
With Option PM Circuit Breaker CB1 Standard Non-Fused Input Disconnect Switch S1
208
Vac
480
Vac
Current Rating
(A)
Wire Size Range
(AWG)
Tightening
Torque (lb. in.)
Current Rating
(A)
Wire Size Range
(AWG)
Tightening
Torque (lb. in.)
D002 B001
30
14-10
or
8-3/0
50
or
120
20 14-8 19
D003 B002
D004 B003
D007 B004
D010 B007
D016 B011
– B014
– B021
45 12-6 40
D024 B027
50
D030 B034
63 6-2 50
– B040
100
– B52L
100 8-2/0 200D046 B052
D059 B065
– B077
150 8-3/0 120
– B096
150
D074 – 115 8-2/0 200
D088 – 150 8-3/0 120
D114 –
175 4-4/0 225
– B124
250
4-40 225
D143 B156
3/0-350 kcmil 225 250 3/0-350 kcmil 225
D169 B180
3.4 Input and Output Power Wiring Connections
62
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual