Object ID Object Name Default Off (0) State On (1) State
BI 10 Multi-Function Output 7 (Z2-23) 0 Off On
BI 11 Multi-Function Output 8 (Z2-24) 0 Off On
BI 12 Multi-Function Output 9 (Z2-25) 0 Off On
BI 13 Safety Interlock Monitor 0 Safety Clear Safety Set
BI 14 HAND/AUTO Reference Monitor 0 AUTO or OFF HAND
BI 15 Multi-Function Input 3 Monitor 0 Off On
BI 16 Multi-Function Input 4 Monitor 0 Off On
BI 17 Multi-Function Input 5 Monitor 0 Off On
BI 18 Multi-Function Input 6 Monitor 0 Off On
BI 19 Multi-Function Input 7 Monitor 0 Off On
u
Metasys N2 Binary Output (BO) Summary
Table F.8 Metasys N2 Binary Output Summary (Bypass to Metasys N2)
Object ID Object Name Default Off (0) State On (1) State
BO 1 Run Forward Command 0 Stop Forward
BO 2 Run Reverse Command 0 Stop Reverse
BO 3 External Fault (EFB) Command 0 No Fault Fault (EFB)
BO 4 Fault Reset Command 0 No Reset Reset
BO 5
<1>
Multi-Function Input 3 (Z2-03) 0 Off On
BO 6
<1>
Multi-Function Input 4 (Z2-04) 0 Off On
BO 7
<1>
Multi-Function Input 5 (Z2-05) 0 Off On
BO 8
<1>
Multi-Function Input 6 (Z2-06) 0 Off On
BO 9
<1>
Multi-Function Input 7 (Z2-07) 0 Off On
BO10
Panel Lock
Note: Not supported
0 – –
BO 11 Communication Fault Enable 0 FB14 Not Activated if Cable Loss Occurs FB14 Activated if Cable Loss Occurs
<1> Disabled when Z3-12 is set to 0 in bypass controller software versions VST800298 and later.
F.6 Metasys N2 Point Database
432
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual