<1> Availalbe in bypass controller software versions VST800298 and later.
n
Z2-31: Safety Open Message Selection
Sets the fault message displayed when an FB01 fault is triggered. This parameter also determines the text that is displayed on
the top line of the HOA keypad.
Note: Parameter available in bypass controller software versions VST800298 and later.
No. Name Setting Range Default
Z2-31 Safety Open Message Selection 0 to 6 0
Setting 0: Safety Open
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
ALM
ALM
BYP-SAFETY OPEN
BYP-FAULTED
DRV/BYP
FB01
Safety Open
RLY FWD
UB-01= 0.0A
RLY
UB-02=10000101
UB-03=00001000
DRV/BYP
LSEQ
LREF
Setting 1: Fire Stat
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
ALM
ALM
BYP-FIRE STAT
BYP-FAULTED
DRV/BYP
FB01
Fire Stat
RLY FWD
UB-01= 0.0A
RLY
UB-02=10000101
UB-03=00001000
DRV/BYP
LSEQ
LREF
Setting 2: Freeze Stat
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
ALM
ALM
BYP-FREEZE STAT
BYP-FAULTED
DRV/BYP
FB01
Freeze Stat
RLY FWD
UB-01= 0.0A
RLY
UB-02=10000101
UB-03=00001000
DRV/BYP
LSEQ
LREF
Setting 3: Smoke Alarm
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
ALM
ALM
BYP-SMOKE ALARM
BYP-FAULTED
DRV/BYP
FB01
Smoke Alarm
RLY FWD
UB-01= 0.0A
RLY
UB-02=10000101
UB-03=00001000
DRV/BYP
LSEQ
LREF
Setting 4: Over Pressure
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
ALM
ALM
BYP-OVR PRESSURE
BYP-FAULTED
DRV/BYP
FB01
Over Pressure
RLY FWD
UB-01= 0.0A
RLY
UB-02=10000101
UB-03=00001000
DRV/BYP
LSEQ
LREF
Setting 5: Low Suction
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
LO
RE
ESC
RUN STOP
ENTERRESET
DIGITAL OPERATOR
ALM
ALM
BYP-LOW SUCTION
BYP-FAULTED
DRV/BYP
FB01
Low Suction
RLY FWD
UB-01= 0.0A
RLY
UB-02=10000101
UB-03=00001000
DRV/BYP
LSEQ
LREF
5.15 Z: Bypass Parameters
210
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual