Property
Object Type
Device
Analog
Input
Analog
Output
Analog
Value
Binary
Output
Binary
Output
Binary
Value
Inactive_Text – – – – Yes Yes Yes
Active_Text – – – – Yes Yes Yes
<1> For Commandable Object Instances only.
u
Analog Input Objects
Table C.4 Analog Input Objects
Object ID Object Name
Modbus
Address
Precision Range Units PV Access
AI1 Analog Input 1 Level 004EH XXXX.X – % R
AI2 Analog Input 2 Level 004FH XXXX.X – % R
AI3 Not used AI3 – – – – –
AI4 Not used AI4 – – – – –
AI5 Not used AI5 – – – – –
AI6 Display Format o1-03 0502H XXXXX – – R
AI7 Scale Format b5-20 01E2H XXXXX – – R
AI8 Inverter Model o2-04 0508F XXXXX – – R
AI9 Rated Current n9-01 05D0H XXXX.X – Amps R
AI10 Motor Current UB-01 8780H XXXX.X – Amps R
AI11 Contactor Voltage 8790H XXXXX – Volts R
u
Analog Output Objects
Table C.5 Analog Output Objects
Object ID Object Name
Modbus
Address
Precision Range Units PV Access
AO1 Analog Output 1 Level 0007H XXXX.X 0 to 100.0 % C
AO2 Analog Output 2 Level 0008H XXXX.X 0 to 100.0 % C
u
Analog Value Objects
Table C.6 Analog Value Objects
Object ID Object Name
Modbus
Address
Precision Range Units PV Access
AV1 Operation Cmd 0001H – – – C
AV2 Frequency Cmd 8401H
XXX.XX
Depends on
o1-03
0.00 to 600.00
Hz
Depends on o1-03
C
AV3 PI Setpoint Cmd 0006H XXX.XX -100.00 to 100.00 % C
AV4 MF Output Cmd 0009H – – – C
AV5 Reference Select Cmd 000FH – – – C
AV6 Drive Status 0020H – – – R
AV7 Fault Details 0021H – – – R
AV8 Data Link Status 0022H – – – R
AV9 Frequency Reference 0040H
XXX.XX
Depends on
o1-03
–
Hz
Depends on o1-03
R
AV10 Output Frequency 0041H
XXX.XX
Depends on
o1-03
–
Hz
Depends on o1-03
R
AV11 Output Voltage 0045H XXXX.X – Volts R
AV12 Output Current 0026H XXXX.X – Amps R
C.6 BACnet Objects Supported
364
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
Kommentare zu diesen Handbüchern