5.8 H: Terminal Functions
H parameters assign functions to the external terminals.
u
H1: Multi-Function Digital Inputs
n
H1-03 to H1-07: Functions for Terminals S3 to S7
These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in Table
5.20.
Note: Setting F has been added and Setting 13 has been removed in bypass controller software versions VST800298 and later.
No. Parameter Name
Setting
Range
Default
H1-03 Multi-Function Digital Input Terminal S3 Function Selection 3 to 60 24: External Fault
H1-04 Multi-Function Digital Input Terminal S4 Function Selection 3 to 60 14: Fault Reset
H1-05 Multi-Function Digital Input Terminal S5 Function Selection 3 to 60 3: Multi-Step Speed Reference 1
H1-06 Multi-Function Digital Input Terminal S6 Function Selection 3 to 60 4: Multi-Step Speed Reference 2
H1-07 Multi-Function Digital Input Terminal S7 Function Selection 3 to 60 6: Jog Reference Selection
Table 5.20 Multi-Function Digital Input Terminal Settings
Setting Function Page
3 Multi-Step Speed Reference 1
151
4 Multi-Step Speed Reference 2
6 Jog reference Selection 151
C Analog Terminal Input Selection 151
F
<1>
Not Used (Through Mode) 151
10 Up Command
151
11 Down Command
Setting Function Page
13
<2>
Reverse Jog 152
14 Fault Reset 153
19 PID Disable 153
24 External Fault 153
60 Motor Pre-Heat 1 153
<1> Available in bypass controller software versions VST800298 and later.
<2> Setting 13: Reverse Jog, is only available in bypass controller software versions VST800297 and earlier.
Settings 3 and 4: Multi-Step Speed Reference 1 and 2
Switches multi-step speed frequency references d1-01 to d1-04 by digital inputs. Refer to d1: Frequency Reference on page
142 for details.
Setting 6: Jog Reference Selection
The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes. Refer to d1:
Frequency Reference on page 142 for details.
Setting C: Analog Terminal Input Selection (Terminals A1 and A2)
When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog
terminals.
Setting F: Not Used (Through Mode)
Note: Available in bypass controller software versions VST800298 and later.
Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function in
the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/
Modbus communications.
Settings 10 and 11: Up/Down Function
The Up/Down function allows the frequency reference to be set by two push buttons when one digital input is programmed
as the Up input (H1-oo= 10) to increase the frequency reference and the other digital input is programmed as the Down input
(H1-oo= 11) to decrease the frequency reference.
The Up/Down function takes priority over the frequency references from the HOA keypad, the analog inputs, and the pulse
input (b1-01 = 0, 1, 4). When using the Up/Down function, references provided by these sources will be disregarded.
The inputs operate as shown in the table below:
5.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
151
5
Programming