Yaskawa MP2000 Series I/O Module User Manual Bedienungsanleitung Seite 94

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 139
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 93
4.2 Specifications of LIO-06 Module Connections
4.2.4 Digital Output Circuit
94
4.2.4 Digital Output Circuit
The following table shows the LIO-06 Module digital output circuit specifications.
Fig. 4.4 Digital Output Circuit (Sink Mode Output)
Item Specifications
Outputs
8 points
Output Format
Transistor, open collector sink mode output
Isolation Method
Photocoupler
Output Voltage
+24 VDC,
±20%
Output Current
100 mA max.
Leakage Current When
OFF
0.1 mA max.
ON Time/OFF Time
ON: 0.25 ms max.
OFF: 1 ms max.
Number of Commons
1 (8 points/common)
Protection Circuit
Fuse
The fuse is not, however, for circuit protection. It is for protecting against fire at output shorts.
Attach a fuse externally to each output if circuit protection is required.
Error Detection
Fuse blown detection
Replace the Module when fuse blown is detected.
Other Functions
DO_07 is shared with counter coincidence output.
0
24
DO_24V
Internal
circuit
DO_OUT
DO_COM
+24V
R
R
Seitenansicht 93
1 2 ... 89 90 91 92 93 94 95 96 97 98 99 ... 138 139

Kommentare zu diesen Handbüchern

Keine Kommentare