Setting : n02 = 0, n03 = 3 or 4
Press the digital operator keys to run or stop the
inverter. Switch run and stop direction by
setting F/R LED.
Set frequency by the analog current signal [0-
100% ( max. frequency ) / 4-20mA or 0-20mA]
connected to the control circuit terminal.
Setting : n02 = 1, n03 = 3 or 4
Switch run/stop and FWD/REV run with
switching device connected to the control circuit
terminal.
Multi-function input terminal S2 is set to
Reverse run / stop (n36 = 2).
Set frequency by the analog current signal [0-
100% ( max. frequency ) / 4-20mA or 0-20mA]
connected to the control circuit terminal.
Frequency reference gain (n41)/bias (n42) can be set even when current reference
input is selected. For details, refer to Adjusting frequency setting signal on
page 45.
Current reference selection
After changing DIP switch (V/I switch of SW8), PRESS on the digital
operator, then set the following constants.
4-20mA....n03 = 3
0-20mA....n03 = 4
PRGM
IM
FS
FR
FC
CURRENT
REFERENCE
4-20mA
OR
0-20mA
(n004=3 OR 4)
IM
FS
FR
FC
S1
S2
SC
CURRENT
REFERENCE
FWD RUN/STOP
REV RUN/STOP
4-20mA
OR
0-20mA
(n004=3 OR 4)