(1) Reduce continuous output current when changing carrier frequency to 4
(10 kHz) for the 200V class (1.5kW or more) and 400V class
inverters. Refer to the table above for the reduced current.
[Operation Condition]
• Input power supply voltage : 3-phase 200 to 230V (200V class)
Single-phase 200 to 240V (200V class)
3-phase 380 to 460V (400V class)
• Ambient temperature : -10 to +50°C (14 to 122°F)
(Protection structure: open chassis type
IP20)
(2) If the wiring distance is long, reduce the inverter carrier frequency as
described below.
(3) Carrier frequency is automatically reduced to 2.5kHz when Reducing
carrier frequency selection at low speed (n75) is set to 1 and the
following conditions are satisfied:
Output frequency 5Hz
Output current 110%
Factory setting : 0 (Disabled)