43
Setting Operation Conditions
“Reverse run disabled” setting does not accept a reverse run command from
the control circuit terminal or digital operator. This setting is used for
applications where a reverse run command can cause problems.
By combining frequency reference and input terminal function selections,
up to 9 steps of speed can be set.
8-step speed change
n02=1 (operation mode selection )
n36=2 (Multi-function contact input terminal 2)
n03=1 (
Frequency reference
selection )
n37=6 (Multi-function contact input terminal 3)
n21=25.0Hz (
Frequency reference 1
)
n38=7 (Multi-function contact input terminal 4)
n22=30.0Hz (
Frequency reference 2)
n39=8 (Multi-function contact input terminal 5)
n23=35.0Hz (
Frequency reference 3
)
n24=40.0Hz (
Frequency reference 4
)
n25=45.0Hz (
Frequency reference 5
)
n26=50.0Hz (
Frequency reference 6
)
n27=55.0Hz (
Frequency reference 7
)
n28=60.0Hz (
Frequency reference 8
)
Reverse run prohibit (n05)
Multi-step speed selection
Reverse run enabled.
Reverse run disabled.
When all multi-function
reference inputs are OFF,
frequency reference selected
by constant n03 (frequency
reference selection) becomes
effective.
n36=2 (Input terminal S2) Initial Setting
n37=6 (Input terminal S3) Change the setting to 6.
n38=7 (Input terminal S4) Change the setting to 7.
n39=8 (Input terminal S5) Change the setting to 8.
Kommentare zu diesen Handbüchern