YASKAWA VS MINI J7 Bedienungsanleitung Seite 37

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 123
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 36
37
Selecting V/f pattern
Adjust motor torque by using V/f pattern and full-range automatic torque
boost.
V/f pattern setting
Set V/f pattern by n09 to n15 as described below. Set each pattern when
using a special motor (high-speed motor, etc.) or when requiring special
torque adjustment of machine.
Be sure to satisfy the following
conditions for the setting of n09 to
n15.
n14 n12 < n11 n09
If n14 = n12 is set, the set value of n13
is disabled.
Adjusting torque according to application
Constants
No.
n09
n10
n11
n12
n13
n14
n15
Max. output frequency
Max. voltage
Max. voltage output
frequency (base frequency)
Mid. output frequency
Mid. output
frequency voltage
Min. output frequency
Min. output
frequency voltage
Name Unit Setting range
Initial
Setting
0.1Hz
1V
0.1Hz
0.1Hz
1V
0.1Hz
1V
50.0 to 400.0Hz 50.0Hz
1 to 255V
(1 to 510V)
*
0.2 to 400.0Hz
1 to 399Hz
1 to 255V
(1 to 510V)*
0.1 to 10.0Hz
1 to 50V
(1 to 100V)*
200V
(400V)
50.0Hz
1.3Hz
12V
(24V)
1.3Hz
12V
(24V)
* For 400-volt class inverters
V: (VOLTAGE)
n10
n13
n15
0
n14 n12 n11 n09
(FREQUENCY)
f
Seitenansicht 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 122 123

Kommentare zu diesen Handbüchern