VS-616G5 Programming Manual 45
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
D Reference Parameters
D1 Preset References
Setting Range: 0.0 to 400.0Hz
Factory Default: 0.0Hz
Up to 9 preset speed references (including jog) can be set through multi-function contact input func-
tion selections. When using the multi-step speed references, set the reference selection (B1-01) to “0”,
and set terminal 16 selection (H3-05) to “1F”. See the following table for programming preset speed
references.
D1-01 Preset Frequency Reference 1 Reference 1
Q Q Q Q
D1-02 Preset Frequency Reference 2 Reference 2
Q Q Q Q
D1-03 Preset Frequency Reference 3 Reference 3
Q Q Q Q
D1-04 Preset Frequency Reference 4 Reference 4
Q Q Q Q
D1-05 Preset Frequency Reference 5 Reference 5
B B B B
D1-06 Preset Frequency Reference 6 Reference 6
B B B B
D1-07 Preset Frequency Reference 7 Reference 7
B B B B
D1-08 Preset Frequency Reference 8 Reference 8
B B B B
Terminal 5
H1-03 = “3”
Terminal 6
H1-04 = “4”
Terminal 7
H1-05 = “5”
Terminal 8
H1-06 = “6”
Speed Reference
Open Open Open Open Speed Reference 1 - Set Reference Source
(B1-01) to “0”.
Closed Open Open Open Speed Reference 2 - Set Terminal 16 Selection
(H3-05) to “1F”.
Open Closed Open Open Speed Reference 3
Closed Closed Open Open Speed Reference 4
Open Open Closed Open Speed Reference 5
Closed Open Closed Open Speed Reference 6
Open Closed Closed Open Speed Reference 7
Closed Closed Closed Open Speed Reference 8
Closed Closed Closed Closed Jog Speed Reference
Section D: Reference Parameters
D1 Preset References