116 VS-616G5 Programming Manual
Section L: Protection Parameters
L8 Hardware Protection
L8 Hardware Protection
The VS-616-G5 comes equipped with a number of built-in functions designed to protect the inverter
and its components from damage. This section describes the set-up of these functions.
When a Yaskawa dynamic braking resistor is used, protection against overheat is enabled with this func-
tion. The duty cycle of the braking resistor is monitored in software so that it does not exceed 3%.
If the duty cycle exceeds 3%, a DB overheat fault (RH) occurs, and the inverter coasts to stop.
Setting Range: 0 to 100°C
Factory Default: 100°C
Sets the heatsink temperature level for protection against overheat (OH).
L8-01 Protection Selection for Internal DB Resistor DB Resistor Prot
B B B B
Setting Description
0 DB resistor overheat protection is not provided (factory default).
1 DB resistor overheat protection is provided.
L8-02 OH Pre-Alarm Level OH Pre-Alarm Lvl
A A A A
0
REV Run Regen
Torque Limit (L7-04)
Positive Torque Reference
Negative Torque Reference
FWD Motor RotationREV Motor Rotation
REV Run Motor
Torque Limit (L7-02)
FWD Run Regen
Torque Limit (L7-03)
FWD Run Motor
Torque Limit (L7-04)
Figure 56 Torque Limit - 4 Quadrant Operation