9.7 Send Message Function (MSG-SND)
9-18
REQUEST
1 = Request
0 = Completion of receipt report
■ Called Station # (PARAM02)
Serial
1~254 : Message is sent to the station of designated device address.
■ Function Code (PARAM04)
The MEMOBUS function code to be sent is set. Refer to Table 9.9.
Table 9.9 Function Codes
Function Code Setting
00H Unused
×
01H Read coil status
○
02H Read input relay status
○
03H Read contents of holding register ○
04H Read contents of input register
○
05H Change status of single coil
○
06H Write into a single holding register
○
07H Unused ×
08H Loop-back test
○
09H Read contents of holding register (expanded)
○
0AH Read contents of input register (expanded)
○
0BH Write into holding register (expanded) ○
0CH Unused
×
0DH Discontinuous readout of holding register (expanded)
○
0EH Discontinuous write into holding register (expanded)
○
0FH Change status of a multiple coil ○
10H Write into a plurality of holding register
○
11H to 20H Unused
×
21H to 3FH System reserved
×
40H to 4FH System reserved ×
50H to Unused
×
(× : cannot be set, ○ :can be set)
Note : Only MW (MB) can be used as the sending/receiving register during master operation. The
MB, MW, IB, and IW registers can be used respectively as the coil, holding register, input
relay, and input registers during slave operation.