86
Other Functions Chapter 6-7
Set Values
The following ON/OFF combinations of UP and DOWN commands are
possible.
With the UP/DOWN function used, the output frequency has the following
restrictions for upper and lower limits.
Upper limit: The maximum frequency in n09 or the frequency reference
upper limit in n30, whichever is smaller.
Lower limit: The minimum output frequency in n14 or frequency reference
lower limit in n31, whichever is smaller.
Value Description
0 The frequency on hold is not retrained.
1 The frequency on hold for 5 s or more is retailed.
Operation of UP/DOWN Function
RUN command
(Forward rotation)
UP command
(S4)
DOWN command
(S5)
Output frequency
Upper limit
Lower limit
Status
Frequency
detection
Time
Time
Time
Time
Time
Note Status U: UP (acceleration)
D: DOWN (deceleration)
H: Hold
U1: Frequency acceleration restricted by upper limit.
D1: Frequency deceleration restricted by lower limit.
Command Acceleration Deceleration Hold Hold
S4 (UP command) ON OFF OFF ON
S5 (DOWN command) OFF ON OFF ON