Function
Constant No.
n==
Function Name Description
Setting
Range
Min.
Setting
Unit
Initial
Ref.
Page
Selecting
Sequence
Input
Functions
36
Multi-function input
selection 2
(Terminal S2)
2 : REV run command (2-wire sequence)
3 : External fault (NO contact input)
4 : External fault (NC contact input)
5 : Fault reset
6 : Multi-step speed reference 1
7 : Multi-step speed reference 2
8 : Multi-step speed reference 3
10 : Jog reference
11 : Accel/Decel time selection
12 : External baseblock (NO contact input)
13 : External baseblock (NC contact input)
14 : Search command from maximum. output frequency
15 : Search command from set frequency
16 : Accel/Decel prohibit
17 : Local/Remote selection
18 : Comm./Control circuit terminal selection
19 : Emergency stop fault (NO contact input)
20 : Emergency stop alarm (NO contact input)
21 : Emergency stop fault (NC contact input)
22 : Emergency stop alarm (NC contact input)
2 to 8
10 to 22
1 2
18
19
21
22
23
37
Multi-function input
selection 3 (Terminal S3)
0 : FWD/REV run command (3-wire sequence)
Other set items are same as n36
0.2 to 8,
10 to 22
1 5
38
Multi-function input
selection 4 (Terminal S4)
Set items are same as n36
2 to 8
10 to 22
1 3
39
Multi-function input
selection 5
(Terminal S5)
Set items are same as n36.
34 : UP/DOWN command (Terminal S4 is UP command/DOWN command and the
setting of n38 is invalid)
35 : Loop test (MEMOBUS)
2 to 8
10 to 22
34, 35
1 6
Selecting
Sequence
Output
Functions
40
Multi-function
output selection 1
(Contact output
terminal
MA-MB-MC)
0 : Fault
1 : Running
2 : Speed agreed
3 : Zero speed
4 : Frequency detection 1 ( Output frequency ≧ Custom frequency detection)
5 : Frequency detection 2 (Output frequency ≦ Custom frequency detection)
6 : Overtorque detection (NO contact output)
7 : Overtorque detection (NC contact output)
10 : Minor fault (alarm displays)
11 : During baselock
12 : Operation mode
13 : Inverter operation ready
14 : During fault retry
15 : Low voltage detecting
16 : In REV running
17 : Speed searching
18 : Output from communication
0 to 7
10 to 18
1 1 25
Selecting
Frequency
Reference
Functions
41*
Analog frequency
reference gain
Sets internal reference level in units of 1 % when frequency reference voltage
(current) is 10V (20mA). Max. output frequency (n09) is 100 %.
0 to 225% 1% 100% 19
42*
Analog frequency
reference bias
Sets internal reference level in units of 1 % when frequency reference voltage
(current) is 0V (4mA or 0mA). Max. output frequency (n09) is 100 %.
–99 to
99%
1% 0% 19
43
Filter time constant for
analog frequency
reference constant
Sets filter time constant for analog input primary lag. (to avoid noise)
0.00 to
2.00s
0.01s 0.10s –
Selecting
Analog
Monitor
Functions
44
Multi-function analog
output
(terminal AM-AC)
0 : Output frequency (10V/Max. frequency n09)
1 : Output current (10V/Inverter rated current)
0, 1 – 0 22
45*
Analog monitor gain
Adjusts output voltage level of analog monitor. (ex.) when 3V is 100 % level,
sets as n45 = 0.30
0.00 to
2.00
0.01 1.00 22
*
Can be changed during operation.
13