Function
Constant No.
n==
Function Name Description
Setting
Range
Min.
Setting
Unit
Initial
Ref.
Page
Selecting
Sequence
Input
Functions
36
Multi-function input
selection 2
(Terminal S2)
2 : REV run command (2-wire sequence)
3 : External fault (NO contact input)
4 : External fault (NC contact input)
5 : Fault reset
6 : Multi-step speed reference 1
7 : Multi-step speed reference 2
8 : Multi-step speed reference 3
10 : Jog reference
11 : Accel/Decel time selection
12 : External baseblock (NO contact input)
13 : External baseblock (NC contact input)
14 : Search command from maximum. output frequency
15 : Search command from set frequency
16 : Accel/Decel prohibit
17 : Local/Remote selection
18 : Comm./Control circuit terminal selection
19 : Emergency stop fault (NO contact input)
20 : Emergency stop alarm (NO contact input)
21 : Emergency stop fault (NC contact input)
22 : Emergency stop alarm (NC contact input)
2 to 8
10 to 22
1 2
18
19
21
22
23
37
Multi-function input
selection 3 (Terminal S3)
0 : FWD/REV run command (3-wire sequence)
Other set items are same as n36
0.2 to 8,
10 to 22
1 5
38
Multi-function input
selection 4 (Terminal S4)
Set items are same as n36
2 to 8
10 to 22
1 3
39
Multi-function input
selection 5
(Terminal S5)
Set items are same as n36.
34 : UP/DOWN command (Terminal S4 is UP command/DOWN command and the
setting of n38 is invalid)
35 : Loop test (MEMOBUS)
2 to 8
10 to 22
34, 35
1 6
Selecting
Sequence
Output
Functions
40
Multi-function
output selection 1
(Contact output
terminal
MA-MB-MC)
0 : Fault
1 : Running
2 : Speed agreed
3 : Zero speed
4 : Frequency detection 1 ( Output frequency Custom frequency detection)
5 : Frequency detection 2 (Output frequency Custom frequency detection)
6 : Overtorque detection (NO contact output)
7 : Overtorque detection (NC contact output)
10 : Minor fault (alarm displays)
11 : During baselock
12 : Operation mode
13 : Inverter operation ready
14 : During fault retry
15 : Low voltage detecting
16 : In REV running
17 : Speed searching
18 : Output from communication
0 to 7
10 to 18
1 1 25
Selecting
Frequency
Reference
Functions
41*
Analog frequency
reference gain
Sets internal reference level in units of 1 % when frequency reference voltage
(current) is 10V (20mA). Max. output frequency (n09) is 100 %.
0 to 225% 1% 100% 19
42*
Analog frequency
reference bias
Sets internal reference level in units of 1 % when frequency reference voltage
(current) is 0V (4mA or 0mA). Max. output frequency (n09) is 100 %.
–99 to
99%
1% 0% 19
43
Filter time constant for
analog frequency
reference constant
Sets filter time constant for analog input primary lag. (to avoid noise)
0.00 to
2.00s
0.01s 0.10s
Selecting
Analog
Monitor
Functions
44
Multi-function analog
output
(terminal AM-AC)
0 : Output frequency (10V/Max. frequency n09)
1 : Output current (10V/Inverter rated current)
0, 1 0 22
45*
Analog monitor gain
Adjusts output voltage level of analog monitor. (ex.) when 3V is 100 % level,
sets as n45 = 0.30
0.00 to
2.00
0.01 1.00 22
*
Can be changed during operation.