Appendix G MSG-SND/MSG-RCV Functions (Ethernet)
G.1 Message Transmit Function (MSG-SND)
A-62
( 6 ) Function Code (PARAM04)
Set a function code to transmit.
The functions (read coil or input relay state, write to holding register, etc.) registered in the function codes are made
available by specifying the code.
The following table shows the function codes available when using a MEMOBUS or Extended MEMOBUS protocol.
Note: 1. B: Bit type, W: Integer type
2. : Available, –: Not available
3. Transmit and receive registers in the master operation mode are MW (MB) only.
4. In slave operation mode, the coil, holding register, input relay, and input register are MB, MW, IB, IW
respectively.
Table G.1 Function Code List (MEMOBUS, Extended MEMOBUS)
Function Code
Targ e t
Data Type
Function
Protocol Type
Extended
MEMOBUS
MEMOBUS
00H
Unused
––
01H
B
Reads coil state
√√
02H
B
Reads input relay state
√√
03H
W
Reads holding register content
√√
04H
W
Reads input register content
√√
05H
B
Changes single coil state
√√
06H
W
Writes to single holding register
√√
07H
Unused
––
08H
Loopback test
√√
09H
W
Reads holding register content (extended)
0AH
W
Reads input register content (extended)
0BH
W
Writes to holding register (extended)
0CH
Unused
––
0DH
W
Discontinuously reads holding register
(extended)
0EH
W
Discontinuously writes to holding register
(extended)
0FH
B
Changes multiple coil states
√√
10H
W
Writes to multiple holding registers
√√