3 Application Selection
YAS K AWA TM.A1000SW.029 Traverse Application A1000 Custom Software Supplement 13
U7-02, Slave Absolute Frequency, (available as an output to the slave by setting parameter H4-01 to 702), has the same
amplitude of 9 Hz (calculated by P1-02
× Reference Frequency). U7-02 is anti-phase to the master waveform and is
centered around U7-04, the Slave Base Frequency. Since the Slave Base Frequency is 45 Hz, U7-02 varies from
36 to 54 Hz while in Traverse mode. Before entering Traverse mode, the Slave Absolute Frequency will rest at 48 Hz, as
represented by the equation in Figure 2.
U7-03, Slave Ripple Frequency, is the same as the U7-02 waveform without the Slave Base Frequency component. Slave
Ripple Frequency U7-03 is a bipolar waveform centered at 0 Hz. The output varies from 21 to 39 Hz during operation.
The Slave Ripple Frequency will rest at 3 Hz before entering Traverse mode as represented by the equation in Figure 2.
Figure 2
Figure 2 Master and Slave Output Diagram: Standard Operation
Run Command
Frequency
Reference
Disturb UP Status
multi-function output
During Disturbed
multi-unction output
Speed Agree
P1-04 P1-0 5
U7-04
Slave Base
Frequency
U7-02
Slave Absolute
Frequency
P1-02 x
Freq Ref
P1-02 x Freq Ref x P1-03
0 Hz
U7-03
Slave Ripple
Frequency
P1-02 x
Freq Ref
0 Hz
P1-02 x Freq Ref x P1-03
2 - P1-03
P1-02 x Freq Ref x P1-03
P1-02 x Freq Ref
P1-02 x Freq Ref
P1-02 x Freq Ref
2 - P1-03
P1-02 x Freq Ref
P1-02 x Freq Ref x P1-03